Acson Ac Error Codes


Acson Ac Error Codes
Error Codes
Operation / Faulty Indication
E1
Room air sensor contact loose / short. Check room sensor connection / change room sensor
E2
Indoor coil sensor contact open. Check indoor coil sensor connection/change indoor coil sensor
E3
Outdoor coil sensor contact open. Check outdoor coil sensor connection/change outdoor coil sensor
E4
Compressor overload protection / Indoor / Outdoor coil sensor short. If running ampere highly increase, change the compressor. If not, replace the coil sensor
E5
Gas leak. Check for leakage & repair / Top up refrigerant
E6
Pump fault. Clear the clogging at drain pipe. If pump is not working, change the pump
E7
Outdoor coil sensor exists (MS model). Remove outdoor coil sensor
E8
Hardware error (tact switch pin short). Check for the tact switch pin condition
E9
No Feedback from indoor fan. Check indoor fan motor / fan motor wiring
EE
EEPROM defrost


Error Codes
Problem
00
Normal
U0
Insufficient gas
U2
DC voltage out of range
U4
Communication error
U7
Signal transmission error (on outdoor unit PCB)
UA
Installation error
UF
Communication Error (indoor and outdoor) piping and wiring
UH
Anti-freeze function in other room
A1
Indoor PCB error
A3
Water pump error
A5
Antifreeze
A6
Indoor fan motor abnormal
C4
Indoor heat exchanger thermistor short/ open
C9
Indoor room thermistor short/ open
E1
Outdoor PCB error
E3
High pressure protection
E4
Low pressure protection
E5
Compressor motor lock
E6
Compressor start-up error
E7
Outdoor DC fan motor lock
E8
Ac input over current
E9
EXV error
EA
4-way valve error
F3
Discharge pipe overheat
F6
Heat exchanger overheat
H0
Compressor sensor system abnormality
H3
High pressure switch error
H6
Position sensor abnormality
H8
AC current sensor error
H9
Outdoor air thermistor short / open
J1
Pressure sensor error
J3
Compressor discharge pipe thermistor short /open / misplaced
J5
Suction pipe thermistor short/ open
J6
Outdoor heat exchanger
J7
Subcooling heat exchanger thermistor short/ open
J8
Liquid pipe thermistor short/ open
J9
Gas pipe thermistor abnormality
LC
Communication error (control PCB and inverter PCB)
L1
Outdoor PCB error
L3
Electrical box temperature rise
L4
Heat sink overheat
L5
IPM error / IGBT error
L9
Stall prevention
P1
Open phase or voltage unbalance
P4
Heat sink thermistor short / open
PJ
Capacity setting error

Error Codes
Problem
E01
Require manual reset (possible causes)
E02
Compressor 1 high temperature (overload)
E03
Compressor 2 high temperature (overload)
E04
Compressor 3 high temperature (overload)
E05
Compressor 4 high temperature (overload)
E06
Compressor 1 high pressure trip / contact open
E07
Compressor 2 high pressure trip / contact open
E08
Compressor 3 high pressure trip / contact open
E09
Compressor 4 high pressure trip / contact open
E10
Compressor 1 trip/low refrigerant/outdoor abnormal
E11
Compressor 2 trip/low refrigerant/outdoor abnormal
E12
Compressor 3 trip/low refrigerant/outdoor abnormal
E13
Compressor 4 trip/low refrigerant/outdoor abnormal
E14
Room sensor short
E15
Room sensor open
E16
Indoor coil sensor 1 short
E17
Indoor coil sensor 2 short
E18
Indoor coil sensor 3 short
E19
Indoor coil sensor 4 short
E20
Indoor coil sensor 1 open
E21
Indoor coil sensor 2 open
E22
Indoor coil sensor 3 open
E23
Indoor coil sensor 4 open
E24
Outdoor coil sensor 1 short
E25
Outdoor coil sensor 2 short
E26
Outdoor coil sensor 2 short
E27
Outdoor coil sensor 4 short
E28
Outdoor coil sensor 1 open
E29
Outdoor coil sensor 2 open
E30
Outdoor coil sensor 3 open
E31
Outdoor coil sensor 4 open
E32
Compressor 1 de-ice
E33
Compressor 2 de-ice
E34
Compressor 3 de-ice
E35
Compressor 4 de-ice

Error Codes
Problem
F3
Sensor Broken (indoor outlet coil)
F4
Sensor Broken (indoor return air)
F5
Indoor and controller communication malfunction
F6
Indoor and controller communication malfunction
F7
Ambient temp exceeds the limit
F8
4WV malfunction
F9
Refrigerant leakage
FA
Controller storage malfunction
FB
Water Pump (indoor water pump)
FC
Indoor and outdoor communication malfunction
FE
Master and slave communication malfunction
H0
Digital comp overload
H1
Fixed Comp1 overload
H2
Fixed Comp2 overload
H3
Fixed Comp3 overload
H4
High pressure too high
H5
Sensor is broken, high pressure
H6
Discharge temp too high
L0
Superheat too low
L1
Low pressure too low
L2
Sensor broken, low pressure
10
System malfunction
11
Sensor broken (slave TH1 discharge temp)
12
Sensor broken (slave TH2 inlet coil 1#)
13
Sensor Broken (slave TH3 mid coil 1#)
14
Sensor broken (slave TH4 inlet coil 2#)
15
Sensor broken (slave TH5 mid coil 2#)
16
Sensor broken (slave TH6 inlet coil 3#)
17
Sensor broken (slave TH7 mid coil 3#)
18
Sensor broken (slave TH8 ambient temp)
19
Sensor broken (slave TH9 outlet coil)
1A
Sensor broken (slave TH10 subcool outlet)
1B
Sensor broken (slave TH11 subcool suction)
1C
Sensor Broken (slave TH12 suction)
1F
Emergency run (slave)
20
Outdoor storage (slave)
27
Ambient temp exceeds the limit (slave)
28
4WV malfunction (slave)
29
Refrigerant leakage (slave)
30
Digital comp overload (slave)
31
Fixed comp1 overload (slave)
32
Fixed comp2 overload (slave)
33
Fixed comp 3 overload (slave)
34
High pressure too high (slave)
35
Sensor broken, high pressure (slave)
36
Discharge temp too high (slave)
40
Super heat too low (slave)
41
Low pressure too low (slave)
42
Sensor broken, low pressure (slave)

Acson Ac Error Codes And Troubleshooting Method

Listed here is the Acson Air Conditioner Error Codes and how to troubleshoot. The Acson AC Error Codes tells you that there is an issue. This Acson AC Error Code will tell you weather the error is from withing the AC or is it due to something external unit. If you know the Meaning of the Error code then it will be very easy to troubleshoot and resolve the issue and fix Acson AC quickly and easily. Just Check the manual, then get it serviced or have it repaired or replace it. We have given the Error Code List for Acson Air Conditioners.
If any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault conditions and causes for some simple troubleshooting tips.
Fault: The compressor does not operate 3 minutes after the air conditioner unit is started.
Causes / Action: -When We See Protection against frequent starting. Wait for 3 to 4 minutes for the compressor to start operating.
Fault: The air conditioner unit does not operate After We see This Type Of Errors.
Causes / Action:
<<<Acson Ac Error Codes And Troubleshooting Method>>>
– Power failure, or the fuse needs to be replaced.
– The power plug is disconnected.
– It is possible that your delay timer has been set incorrectly.
– If the fault persist after all these verifications, please contact the air conditioner unit installer.
Fault: The air flow is too low

Wireless Remote Controller

  • The compact LCD transmitter is able to operate the air conditioner unit within the distance of 9 metres.
  • Fan motor speed can be set at low / medium / high or automatic.
  • Sleep mode auto control will gradually increase or decrease the setting temperature to provide a
    comfortable surrounding for sleeping.
  • Air flow direction can be controlled automatically.
  • Room temperature is controlled by electronic thermostat.
  • The real time timer allows the air conditioner to be switched on and off automatically based on user
    settings.
  • Turbo mode function is available to enables the required set temperature to be achieved in a short time
  • Personalized setting allows user to preset and store 2 groups of personal settings (including timer setting)
    in the handset.


voltas AC unlock passwords