Indoor Unit Error Codes
| Error Code | Description | Possible Cause | Objects | |||||
|---|---|---|---|---|---|---|---|---|
| RA | SkyAir | VRV | Package | HRV | Chiller | |||
| A0 | External protection device activated | External protection device connected to the terminal strip T1-T2 of indoor unit is activated | ◯ | ◯ | ◯ | |||
| A1 | Malfunction of indoor unit PCB | Malfunction due to noise Defect of indoor unit PCB | ◯ | ◯ | ◯ | ◯ | ||
| A3 | Malfunction of drain level control system | Drain piping clogging, improper drain piping work Defect of drain pump Defect of float switch | ◯ | ◯ | ◯ | |||
| A4 | Malfunction of freezing protection | Shortage of water volume Low water temperature setting Defect of 26WL Defect of water temperature thermistor | ◯ | |||||
| A5 | High pressure control in heating, freeze-up protection control in cooling | Clogged air filter of indoor unit and short-circuit Defect of indoor unit heat exchanger thermistor | ◯ | |||||
| A6 | Fan motor locked, overload, overcurrent | Defect of connector contact Defect of indoor unit PCB | ◯ | ◯ | ◯ | ◯ | ||
| A7 | Malfunction of swing flap motor | Failure of swing flap motor Defect of indoor unit PCB Jammed swing mechanism/blade | ◯ | ◯ | ||||
| A8 | Malfunction of power supply | Overcurrent of AC input | ◯ | ◯ | ||||
| A9 | Malfunction of electronic expansion valve drive | Defect of electronic expansion valve coil Defect of indoor unit PCB Defect of connector contact | ◯ | ◯ | ||||
| AA | Heater overheat | 26WH is activated | ◯ | |||||
| AF | Malfunction of a humidifier system | Water leakage of humidifier (option) Failure of swing float switch Improper drain piping incline | ◯ | ◯ | ||||
| AH | Malfunction of dust collector of air cleaner | Defect of dust collecting element Defect of high voltage power supply unit Stained insulator part Defect of indoor unit PCB | ◯ | ◯ | ◯ | |||
| AJ | Malfunction of capacity setting (Indoor unit PCB) | Capacity setting adaptor is not installed when replacing PCB Defect of indoor unit PCB | ◯ | ◯ | ◯ | |||
| C1 | Failure of transmission (between indoor unit PCB and fan PCB) | Defect of transmission of fan motor control driver | ◯ | ◯ | ||||
| C4 | Malfunction of liquid pipe thermistor for heat exchanger | Defect of connector contact Defect of liquid pipe thermistor for heat exchanger | ◯ | ◯ | ◯ | ◯ | ||
| C5 | Malfunction of gas pipe thermistor for heat exchanger | Defect of connector contact Defect of gas pipe thermistor for heat exchanger | ◯ | ◯ | ◯ | |||
| C6 | Malfunction of fan motor control driver | Defect of fan motor sensor system Defect of fan motor control driver | ◯ | ◯ | ||||
| C7 | Front panel driving motor fault | Defect of front panel driving motor Defect of limit switch | ◯ | |||||
| C9 | Malfunction of suction air thermistor | Defect of connector contact Defect of thermistor for suction air | ◯ | ◯ | ◯ | ◯ | ||
| CA | Malfunction of discharge air thermistor | Defect of connector contact Defect of thermistor for discharge air | ◯ | ◯ | ||||
| CC | Malfunction of humidity sensor system | Defect of connector contact Defect of humidity sensor | ◯ | ◯ | ||||
| CJ | Malfunction of thermostat sensor in remote controller | Defect of remote controller thermistor Malfunction due to noise Defect of remote controller PCB | ◯ | ◯ | ◯ | |||
Outdoor Unit Error Codes
| Error Code | Description | Possible Cause | Objects | |||||
|---|---|---|---|---|---|---|---|---|
| RA | SkyAir | VRV | Package | HRV | Chiller | |||
| E0 | Protection devices actuated (unified) | Protection device connected to outdoor PCB actuated Defect of protection device connector contact | ◯ | ◯ | ◯ | |||
| E1 | Defect of outdoor unit PCB | Malfunction due to noise Defect of outdoor unit PCB | ◯ | ◯ | ◯ | ◯ | ◯ | |
| E3 | Actuation of high pressure switch (HPS) | Dirty outdoor unit heat exchanger and suction filter Defect of HPS Clogged refrigerant piping Defect of connector contact | ◯ | ◯ | ◯ | ◯ | ||
| E3 | System No.1 Actuation of high pressure switch (HPS) | Dirty outdoor unit heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact | ◯ | |||||
| E4 | Actuation of low pressure switch (LPS) | Clogged refrigerant piping Shortage of gas Defect of connecting connector Defect of outdoor unit PCB Clogged refrigerant piping Shortage of gas Defect of connecting connector Defect of outdoor unit PCB | ◯ | ◯ | ◯ | ◯ | ||
| E5 | Overheat of inverter compressor motor | Shortage of refrigerant amount Defect of connector contact Leakage of four way valve | ◯ | ◯ | ||||
| E5 | Inverter compressor motor lock | Inverter compressor lock Incorrect wiring | ◯ | ◯ | ◯ | |||
| E6 | STD compressor motor overcurrent/lock | Closed stop valve STD compressor lock | ◯ | ◯ | ◯ | ◯ | ||
| E6 | System No.1 Compressor overcurrent | Defect of EXP. valve Defect of compressor Shortage of refrigerant amount | ◯ | |||||
| E7 | Malfunction of outdoor unit fan motor | Faulty contact of fan motor connector Defect of fan motor Defect of fan motor driver | ◯ | ◯ | ◯ | ◯ | ◯ | |
| E8 | Overcurrent of inverter compressor | Defect of compressor Defect of outdoor unit PCB Defect of inverter main circuit capacitor Defect of power transistor | ◯ | |||||
| E9 | Malfunction of electronic expansion valve coil | Defect of electronic expansion valve Defect of connector contact Defect of outdoor unit PCB | ◯ | ◯ | ◯ | ◯ | ||
| EA | Malfunction of four way valve | Defect of four way valve Defect of outdoor unit PCB Shortage of gas Defect of thermistor | ◯ | |||||
| EC | Malfunction of entering water temperature | Malfunction of cooling water temperature Defect of thermistor Defect of outdoor unit PCB | ◯ | |||||
| EF | Malfunction of thermal storage unit | Defect of electronic expansion valve of thermal storage unit Defect of thermal storage PCB | ◯ | |||||
| F3 | Malfunction of discharge pipe temperature | Shortage of gas Defect of connector contact Clogged refrigerant piping Defect of discharge pipe thermistor | ◯ | ◯ | ◯ | ◯ | ◯ | |
| F6 | Abnormal high pressure in cooling | Defect of outdoor unit fan motor Defect of electronic expansion valve Defect of heat exchanger thermistor Defect of outdoor unit PCB | ◯ | |||||
| F6 | Refrigerant overcharged | Refrigerant overcharged Disconnection of heat exchanger thermistor Disconnection of outdoor air thermistor Disconnection of liquid pipe thermistor | ◯ | ◯ | ||||
| Error Code | Description | Possible Cause | Objects | |||||
|---|---|---|---|---|---|---|---|---|
| RA | SkyAir | VRV | Package | HRV | Chiller | |||
| H0 | Malfunction of sensor system of compressor | Harness is disconnected, or defective connection Defect of PCB | ◯ | |||||
| H1 | Malfunction of humidifier unit damper | Defect of limit switch Defect of damper | ◯ | |||||
| H3 | Malfunction of high pressure switch (HPS) | Defect of high pressure switch Broken wire Defect of connector contact Defect of outdoor unit PCB | ◯ | ◯ | ◯ | ◯ | ||
| H4 | Malfunction of low pressure switch (LPS) | Defect of low pressure switch Broken wire Defect of connector contact Defect of outdoor unit PCB | ◯ | ◯ | ||||
| H5 | Malfunction of compressor motor overload thermistor | Defect of connector contact Defect of compressor motor overload thermistor | ◯ | |||||
| H6 | Malfunction of position detection sensor | Faulty contact of compress or cable Defect of compressor Defect of outdoor unit PCB | ◯ | |||||
| H7 | Malfunction of outdoor fan motor signal | Faulty contact of fan wiring Defect of fan motor driver Defect of fan motor | ◯ | ◯ | ◯ | |||
| H8 | Malfunction of compressor input (CT) system | Defect of power transistor Defect of reactor | ◯ | |||||
| H9 | Malfunction of outdoor air thermistor | Defect of connector contact Defect of thermistor for outdoor air | ◯ | ◯ | ◯ | ◯ | ◯ | |
| HC | Malfunction of (hot) water temperature thermistor | Defect of connector contact Defect of outdoor unit PCB Defect of thermistor for water temperature | ◯ | ◯ | ||||
| HF | Alarm in thermal storage unit with ice | Thermal storage group defective wiring Defect of setting Excess of thermal storage tank numbers | ◯ | ◯ | ||||
| HJ | Malfunction of thermal storage tank water level | Low water level Defect of switch setting Water level detecting sensor failure Defect of connector contact | ◯ | ◯ | ||||
| J1 | Malfunction of pressure sensor | Defect of pressure sensor connector contact Defect of pressure sensor Defect of outdoor unit PCB | ◯ | ◯ | ||||
| J2 | Malfunction of current sensor of compressor | Defect of current sensor Defect of outdoor unit PCB Defect of compressor | ◯ | ◯ | ◯ | ◯ | ||
| J3 | Malfunction of discharge pipe thermistor | Defect of connector contact Defect of outdoor unit PCB Defect of discharge pipe thermistor | ◯ | ◯ | ◯ | ◯ | ◯ | |
| J4 | Malfunction of low pressure equivalent saturated temperature sensor system | Defect of connector contact Defect of thermistor Defect of outdoor unit PCB (Multi-split, Super-multi ) | ◯ | |||||
| J5 | Malfunction of suction pipe thermistor | Defect of connector contact Defect of outdoor unit PCB Defect of suction pipe thermistor | ◯ | ◯ | ◯ | ◯ | ◯ | |
| J6 | Malfunction of heat exchanger thermistor | Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor | ◯ | ◯ | ◯ | ◯ | ◯ | |
| J7 | Malfunction of liquid pipe thermistor (Refrigerant circuit and others) | Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor | ◯ | ◯ | ◯ | ◯ | ||
| J8 | Malfunction of liquid pipe thermistor (Refrigerant circuit and others) | Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor | ◯ | |||||
| J9 | Malfunction of gas pipe thermistor (Refrigerant circuit and others) | Defect of connector contact Defect of outdoor unit PCB Defect of gas pipe thermistor | ◯ | ◯ | ◯ | ◯ | ||
| JA | Malfunction of high pressure sensor | Defect of connector contact Defect of outdoor unit PCB Defect of high pressure sensor | ◯ | ◯ | ◯ | ◯ | ||
| JC | Malfunction of low pressure sensor | Defect of connector contact Defect of outdoor unit PCB Defect of low pressure sensor | ◯ | ◯ | ◯ | ◯ | ||
| JE | Malfunction of sub-tank thermistor | Defect of connector contact Defect of outdoor unit PCB Defect of sub-tank thermistor | ◯ | |||||
| JF | Malfunction of heating thermistor for heat exchanger | Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor | ◯ | |||||
| JH | Malfunction of oil temperature thermistor | Defect of connector contact Defect of outdoor unit PCB Defect of oil temperature thermistor | ◯ | |||||
| Error Code | Description | Possible Cause | Objects | |||||
|---|---|---|---|---|---|---|---|---|
| RA | SkyAir | VRV | Package | HRV | Chiller | |||
| L0 | Malfunction of inverter system | Shortage of power supply capacity Defect of inverter PCB Defect of power transistor | ◯ | |||||
| L1 | Malfunction of inverter PCB | Defect of compressor wiring Blown fuse Defect of outdoor unit fan motor Defect of inverter PCB | ◯ | ◯ | ||||
| L3 | Electrical box temperature rise | Fin temperature rise due to short-circuit Defect of power transistor Defect of outdoor unit fan Defect of outdoor unit PCB | ◯ | |||||
| L4 | Malfunction of inverter radiating fin temperature rise | Fin temperature rise due to short-circuit Defect of fin thermistor | ◯ | ◯ | ◯ | ◯ | ||
| L5 | Inverter instantaneous overcurrent (DC) | Closed stop valve Defect of compressor | ◯ | ◯ | ◯ | ◯ | ||
| L6 | Inverter instantaneous overcurrent (AC) | Overcharge of refrigerant amount Defect of compressor Shortage of power supply capacity Defect of inverter unit | ◯ | |||||
| L8 | Overcurrent of inverter compressor | Abnormal high pressure rise due to clogged refrigerant circuit and others Defect of compressor | ◯ | ◯ | ◯ | |||
| L9 | Malfunction of inverter compressor startup | Faulty of pressure equalization Defect of compressor wiring Defect of compressor | ◯ | ◯ | ◯ | |||
| LA | Malfunction of power transistor | Defect of power transistor Defect of inverter PCB Defect of compressor | ◯ | |||||
| LC | Malfunction of transmission between outdoor unit PCB and micro-computer | Defect of grounding connection Defect of outdoor unit PCB Malfunction due to noise | ◯ | |||||
| LC | Malfunction of transmission between control and inverter PCB | Defect of connector contact Defect of inverter PCB Malfunction due to noise Defect of outdoor unit control PCB | ◯ | ◯ | ◯ | |||
| P0 | Shortage of refrigerant amount (thermal storage unit) | Shortage of refrigerant Clogged refrigerant piping | ◯ | |||||
| P1 | Power voltage imbalance, open phase | Open phase Voltage imbalance between phases Faulty main circuit capacitor Defect of wiring contact | ◯ | ◯ | ◯ | ◯ | ||
| P2 | Automatic refrigerant charge operation stop | Closed stop valve Closed valve of refrigerant tank | ◯ | ◯ | ||||
| P3 | Malfunction of thermistor in electrical box | Electrical box temperature rise (ambient temperature rise) Defect of fin thermistor Defect of outdoor unit PCB | ◯ | ◯ | ||||
| P4 | Malfunction of radiating fin temperature sensor | Defect of radiating fin thermistor Defect of wiring contact Defect of outdoor unit PCB | ◯ | ◯ | ◯ | ◯ | ||
| P8 | Heat exchanger freezing protection during automatic refrigerant charging | (Close the refrigerant cylinder. Start again from step 1.) | ◯ | ◯ | ||||
| P9 | Malfunction of fan motor (humidifier unit) | Defect of fan motor Broken relay harness Defect of outdoor unit PCB Defect of connector contact | ◯ | |||||
| P9 | Automatic refrigerant charge operation completed | N/A | ◯ | ◯ | ||||
| PA | Broken wire of heater (humidifier unit) | Defect of heater unit Defect of outdoor unit PCB Defect of thermistor | ◯ | |||||
| PA | Empty refrigerant cylinder during automatic refrigerant charging | Refrigerant cylinder of master unit is empty | ◯ | ◯ | ||||
| PC | Empty refrigerant cylinder during automatic refrigerant charging | Refrigerant cylinder of slave unit 2 is empty | ◯ | ◯ | ||||
| PE | Automatic refrigerant charge operation nearly completed | N/A | ◯ | ◯ | ||||
| PH | Malfunction of temperature (humidifier unit) | Defect of heater unit Defect of thermistor Defect of connector contact Defect of outdoor unit PCB | ◯ | |||||
| PH | Empty refrigerant cylinder during automatic refrigerant charging | Refrigerant cylinder of slave unit 1 is empty | ◯ | ◯ | ||||
| PJ | Malfunction of capacity setting (Outdoor unit PCB) | Capacity setting adaptor is not installed Improper capacity setting adaptor Defect of outdoor unit PCB | ◯ | |||||
| PJ | Improper combination between inverter and fan driver | Mistake of inverter PCB Mistake of control PCB Mistake of inverter fan PCB | ◯ | ◯ | ||||
System Error Codes
| Error Code | Description | Possible Cause | Objects | |||||
|---|---|---|---|---|---|---|---|---|
| RA | SkyAir | VRV | Package | HRV | Chiller | |||
| U0 | Shortage of refrigerant | Shortage of refrigerant Closed stop valve Clogged refrigerant piping | ◯ | ◯ | ◯ | ◯ | ◯ | |
| U1 | Reverse phase, open phase | Reverse phase Open phase of power wiring Wrong wiring Defect of outdoor unit PCB | ◯ | ◯ | ◯ | ◯ | ◯ | |
| U2 | Defect of power supply voltage or instantaneous power failure | Defect of power supply voltage Instantaneous power failure Defect of wiring contact | ◯ | ◯ | ◯ | ◯ | ||
| U3 | Check operation not executed | Check operation not executed | ◯ | ◯ | ||||
| U3 | Malfunction of transmission | Malfunction due to noise Defect of outdoor unit PCB Wrong wiring | ◯ | |||||
| U4 | Malfunction of transmission between indoor and outdoor unit | Defect or indoor-outdoor transmission wiring Malfunction due to noise Defect of indoor unit PCB and outdoor unit PCB | ◯ | ◯ | ◯ | ◯ | ◯ | |
| U5 | Malfunction of transmission between indoor unit and remote controller | Defect of remote controller wiring Defect of indoor unit PCB Malfunction due to noise Defect of remote controller main/sub setting | ◯ | ◯ | ◯ | ◯ | ◯ | ◯ |
| U6 | Malfunction of transmission between indoor units | Faulty wiring Defect of indoor unit PCB Malfunction due to noise | ◯ | |||||
| U7 | Malfunction of transmission between main body micro-computer – INV micro-computer | Harness disconnection/broken wire between PCB Defect of outdoor unit PCB | ◯ | |||||
| U7 | Malfunction of transmission between outdoor units | Defect of wiring between outdoor units Defect of outdoor unit switch setting Defect of wiring between outdoor – thermal storage units | ◯ | ◯ | ◯ | |||
| U8 | Malfunction of transmission between remote controllers | Defect of remote controller main/sub setting Defect of remote controller wiring Defect of remote controller PCB | ◯ | ◯ | ◯ | ◯ | ||
| U9 | Malfunction of transmission (other system) | Defect of communication between other indoor unit and outdoor unit Other indoor unit electronic expansion valve failure | ◯ | ◯ | ||||
| UA | Defect of indoor/outdoor power supply | Wrong model connections Wrong PCB connected Improper power supply Defect of PCB | ◯ | |||||
| UA | Malfunction of field setting | Malfunction of field setting by remote controller Defect of remote controller wiring Defective connection of optional device Defect of indoor unit PCB | ◯ | |||||
| UA | Improper combination of indoor and outdoor units | Excess of connected indoor units Malfunction of field setting Uncanceled service mode Defect of outdoor unit PCB | ◯ | ◯ | ◯ | |||
| UA | Remote temperature setting wire disconnection | Remote temperature setting wire disconnection Defect of connector contact | ◯ | |||||
| UC | Malfunction of setting of centralized controller address | Address duplication of centralized controller | ◯ | ◯ | ◯ | |||
| UE | Malfunction of transmission between indoor unit and centralized controller | Malfunction of wiring between indoor unit and centralized controller Defect of setting of group number Defect of indoor unit PCB | ◯ | ◯ | ◯ | ◯ | ◯ | |
| UF | Wiring and piping mismatch | Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor units | ◯ | ◯ | ◯ | |||
| UH | Malfunction of system | Improper connection of transmission wiring between indoor- outdoor units and outdoor-outdoor units Defect of indoor and outdoor unit PCB (RA: Mismatching indoor and outdoor units) Defect of voltage Freeze protection in other indoor unit | (k) | ◯ | ◯ | |||
| UJ | Malfunction of transmission (Accessory devices) | Defect of accessory devices Faulty wiring | ◯ | ◯ | ||||
| M1 | Malfunction of centralized remote controller PCB | Defect of centralized remote controller PCB | ◯ | ◯ | ◯ | ◯ | ◯ | ◯ |
| M8 | Malfunction of transmission between optional controllers for centralized control | Other centralized control power disconnection Centralized control reset switch ON Defect of transmission wiring Central remote controller address change | ◯ | ◯ | ◯ | ◯ | ◯ | ◯ |
| MA | Improper combination of optional controllers for centralized control | Improper combination of optional controllers for centralized control More than one master controller is connected Faulty setting of centralized control Defect of centralized control | ◯ | ◯ | ◯ | ◯ | ◯ | ◯ |
| MC | Address duplication, improper setting | Address duplication of central remote controller | ◯ | ◯ | ◯ | ◯ | ◯ | ◯ |
Other Error Codes
| Error Code | Description | Possible Cause | Objects | |
|---|---|---|---|---|
| HRV | Chiller | |||
| 77 | System No. 1 Malfunction of fan inter lock | Defect of relay contact Broken wire | ◯ | |
| 78 | System No. 2 Malfunction of fan inter lock | Defect of relay contact Broken wire | ◯ | |
| 7A | System No. 2 Malfunction of current sensor of compressor | Defect of current sensor Defect of compressor Defect of outdoor unit PCB | ◯ | |
| 7C | System No. 2 Malfunction of pump inter lock | Cooling water pump interlock actuated | ◯ | |
| 80 | Malfunction of entering water temperature thermistor | Defect of connector contact Defect of entering water temperature thermistor | ◯ | |
| 81 | Malfunction of leaving water temperature thermistor | Defect of connector contact Defect of leaving water temperature thermistor | ◯ | |
| 82 | System No. 1 Malfunction of refrigerant thermistor | Defect of connector contact Defect of refrigerant thermistor | ◯ | |
| 83 | System No. 2 Malfunction of refrigerant thermistor | Defect of connector contact Defect of refrigerant thermistor | ◯ | |
| 84 | System No. 1 Malfunction of heat exchanger thermistor | Defect of connector contact Defect of heat exchanger thermistor | ◯ | |
| 85 | System No. 2 Malfunction of heat exchanger thermistor | Defect of connector contact Defect of heat exchanger thermistor | ◯ | |
| 86 | System No. 2 Malfunction of discharge pipe thermistor | Defect of connecting connector Defect of discharge pipe thermistor | ◯ | |
| 88 | System No. 2 Malfunction of discharge pipe temperature | Shortage of gas Defect of discharge pipe thermistor Defect of connector contact Clogged refrigerant piping | ◯ | |
| 89 | Malfunction of brazed-plate heat exchanger freezing | Dirty heat exchanger Shortage of refrigerant amount Defect of thermistor | ◯ | |
| 8A | System No. 2 Malfunction of leaving water temperature thermistor | Defect of connector contact Defect of leaving water temperature thermistor | ◯ | |
| 8E | System No. 1 Malfunction of suction pipe thermistor 1 for heating | Defect of connector contact Defect of suction pipe thermistor | ◯ | |
| 8F | System No. 1 Malfunction of suction pipe thermistor 2 for heating | Defect of connector contact Defect of suction pipe thermistor | ◯ | |
| 8H | Abnormal high hot water temperature | Three-way valve malfunction Defect of thermistor Defect of water temperature setting | ◯ | |
| 90 | Abnormal chilled water quantity, abnormal AXP | Shortage of water volume Disconnection of AXP | ◯ | |
| 91 | System No. 2 Malfunction of electronic expansion valve | Defect of connector contact Defect of electronic expansion valve coil | ◯ | |
| 92 | System No. 2 Malfunction of suction pipe thermistor | Defect of connector contact Defect of suction pipe thermistor | ◯ | |
| 94 | Malfunction of transmission (between heat reclaim ventilation unit and fan unit) | Defect of fan unit PCB Defect of connecting wire between (1) and (2) | ◯ | |
| 95 | System No. 1 Malfunction of inverter system | Defect of fan inverter unit | ◯ | |
| 96 | System No. 1 Malfunction of inverter system | Defect of fan inverter unit | ◯ | |
| 97 | Malfunction of thermal storage unit | Defect of thermal storage unit | ◯ | |
| 98 | Malfunction of thermal storage brine pump | Actuation of thermal storage brine pump overcurrent (OC) | ◯ | |
| 99 | Malfunction of thermal storage brine tank | Low water level of thermal storage brine tank | ◯ | |
| 60 | External protection device actuated | Actuation of external protection device Defect of output signal wiring Defect of control PCB | ◯ | |
| 64 | Malfunction of indoor air thermistor | Defect of connecting connector Defect of thermistor for indoor air Defect of control PCB | ◯ | |
| 65 | Malfunction of outdoor air thermistor | Defect of connector contact Defect of control PCB Defect of outdoor air thermistor | ◯ | |
| 6A | Malfunction of damper system | Defect of connector contact Defect of damper motor Defect of limit switch Defect of control PCB | ◯ | |
| 70 | System No. 2 Compressor overload | Shortage of refrigerant amount Defect of connector contact Leakage of four way valve | ◯ | |
| 71 | System No. 2 Compressor overcurrent | Shortage of refrigerant amount Short-circuit Defect of compressor | ◯ | |
| 72 | System No. 2 Fan motor overcurrent | Defect of fan motor connector contact Defect of fan motor Defect of PCB | ◯ | |
| 73 | System No. 2 Malfunction of high pressure (HPS) actuated | Dirty heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact | ◯ | |
| 74 | System No. 2 Malfunction of low pressure switch (LPS) | Clogged refrigerant piping Shortage of gas Defect of connector contact Defect of LPS | ◯ | |
| 75 | System No. 2 Malfunction of low pressure sensor | Defect of connector contact Defect of PCB Defect of low pressure sensor | ◯ | |
| 76 | System No. 2 Malfunction of high pressure sensor | Defect of connector contact Defect of PCB Defect of high pressure sensor | ◯ | |