LG AC & Air conditioner Error Codes

Error CodePossible Cause
ch01Indoor unit room temperature sensor error
ch02Indoor unit inlet pipe sensor error
ch04Float switch error (optional)
ch05Communication error between indoor unit and outdoor units
ch06Indoor unit outlet pipe sensor error
ch09Indoor unit EPROM error
ch10Indoor unit BLDC motor fan lock
ch12Indoor unit middle pipe sensor error
ch21DC Peak (IPM Fault); Compressor DC voltage was too high
ch22Current Transformed (CT2) error; Alternating current (AC) input too high
ch23DC Link Low Volt
ch25AC Low/High Volt
ch26DC Comp Position Error (not providing rotation), Locking
ch27PSC Fault; Current to inverter compressor between AC and DC converter circuit too high
ch28Inverter compressor DC voltage is too high
ch29Inverter compressor amperage is too high
ch31Current-to-current transformer (CT) thermistor is too low
ch32Inverter Compressor Discharge Pipe (D-Pipe) Overheat
ch40CT Sensor Error; Thermistor is disconnected or shorted out
ch41D-Pipe Sensor INV is disconnected or shorted out
ch44Outdoor Air Sensor is disconnected or shorted out
ch45Middle thermistor of outdoor unit condenser coil is disconnected or shorted out
ch46Outdoor unit suction line thermistor is disconnected or shorted out
ch48Outdoor unit coil outlet (liquid line) thermistor is disconnected or shorted out
ch53Communication failure from outdoor unit to indoor unit
ch60Outdoor unit printed circuit board (PCB) EPROM check sum error
ch61Outdoor unit condenser coil temperature is too high
ch62Outdoor unit inverter compressor PCB heat sink temperature is too high
ch63Condenser coil pipe thermistor temperature is too low
ch65Heat sink thermistor has disconnected or has shorted out
ch67Outdoor brushless direct current (BLDC) fan motor lock error

Error CodePossible CauseSolution
Code appears in the display. F1,F2 or F3Air conditioner is in FAN mode and the number shown is the set fan speed.This is normal. The air conditioner is working properly.
FLThe water collection tank is full.Empty the water collection tank.
CH01Short or open circuit in the indoor air thermistor.Unplug the air conditioner and contact your authorized LG service center.

Error CodeDescriptionLED 01G/M (Red)LED 01G/M (Red)Possible Cause
21DC Link Peak (IPM Fault)2 times 31 times 3Over Rated Current
22CT 2 (Max CT)2 times 3Input Over Current
23DC Link Low Volt.
DC Link High Volt.
3 times 3DC Link Volt is below 140Vdc
DC Link Volt is above 420Vdc
25Low Voltage/Over Voltage5 times 3Abnormal AC Volt Input
26DC Compressor Position Error6 times 3Compressor Starting Fall Error
27PSC/PFC Fault Error7 times 3Over Inverter PCB input current
29COMP Over Current9 times 3Over Inverter Compressor Current
32D-Pipe High3 times 32 times 3D-Pipe Temp. High
35Low Pressure Error5 times 3Excessive decrease of Low Pressure
39Communication Error9 times 3Communication Error Between PFC Micom and INV Micom
40CT Sensor (Open/Short)4 times 30CT Circuit Malfunction
41INV. D-Pipe Th Error1 times 3Open/Short
43High Pressure Sensor Error3 times 3
44Outdoor Air Th Error4 times 3
45Cond. Mid-Pipe Th Error5 times 3
46Suction Pipe Th Error6 times 3
48Cond. Out-Pipe Th Error8 times 3
51Capacity Over5 times 31 times 3Over combination
53Signal Error (Indoor <-> Outdoor)3 times 3Communication Poorly
543-Phase Wrong wiring4 times 33-Phase Wrong Wring of Outdoor Unit (Reverse Phase/Omission of Phase)
60EEPROM Check Sum Error6 times 30Check Sum Mismatching
61Cond. Pipe Th High1 times 3Cond. Temp. High
62Heat sink Th High2 times 3Heatsink Temp. High
65Heat sink Th Error5 times 3Open/Short
67Outdoor BLDC Fan Lock7 times 3Outdoor Fan is not operation
73PFC Fault Error(SAN)7 times 33 times 3Over Current of Outdoor Unit PFC

Error CodeDescriptionPossible CauseCheck point and normal condition
1Indoor air sensor• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor: 10KS2/ at 25°C (Unplugged)
Normal voltage : 2.5Vdc / at 25°C (plugged)
2Indoor inlet pipe sensor• Open / Short
• Soldered poorly
Normal resistor: 5K£2/ at 25°C (Unplugged)
Normal voltage : 2.5Vdc / at 25°C (plugged)
6Indoor outlet pipe sensor• Internal circuit error-
3Communication• Open / Short• Connection of wire
3Wired R/C• Wrong connection• Main PCB Volt. DC 12V
• Noise interference
4Drain pump/Float switch• Float switch Open. (Normal: short)• The connection of wire(Drain pump/ Float switch)
• Drain pump power input. (220V)
• Drain tube installation.
• Indoor unit installation. (Inclination)
апр.53Communication (Indoor - Outdoor)• Communication poorly• Power input AC 220V. (Outdoor, Indoor)
• The connector for transmission is disconnected.
• The connecting wires are misconnected.
• The GND1,2 is not connected at main GND.
• The communication line is shorted at GND.
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.
21DC Peak• Instant over current
• Over Rated current
• Poor insulation of IPM
• An instant over current in the U,V,W phase
- Comp lock
- The abnormal connection of U,V,W
• Over load condition
- Overcharging of refrigerant
- Pipe length.
• Poor insulation of compressor
22Max. C/TOver current (14A)Malfunction of compressor
Blocking of pipe
Low voltage input
Refrigerant, pipe length, blocked
40CFT Internal circuitInitial current errorMalfunction of current detection circuit.
(Open / Short)
The voltage of “C01N" Is 4.0Vdc(25A).
23DC Link• DC link volt, is 140Vdc.• Check the power source.
23Low voltage.-• Check the components.
28DC Link High voltage• DC link volt, is 420Vdc T-
24Press S/W Open• Low / High press• Check the connection of “CN_Press”.
• Check the components.
25Input voltage• Abnormal Input voltage• Check the power source.
• Check the components.
26DC Compressor Position• Compressor position detect error• Check the connection of comp wire “U,V,W”
• Malfunction of compressor
• Check the component of “IPM", detection parts.
27PSC Fault• Over current at "IGBT"• Check the component of “IGBT".
• Check the components.
32D-pipe (Inverter) temp, high (105°C t)• Discharge sensor (Inverter) temp, high• Check the discharge pipe sensor for INV.
• Check the install condition for over load.
• Check the leakage of refrigerant.
• Check the SVC V/V open.
33D-pipe (Constant) temp, high (105°C I)• Discharge sensor (Cons.) temp, high• Check the discharge pipe sensor for Cons.
• Check the install condition for over load.
• Check the leakage of refrigerant.
• Check the SVC V/V open.
41D-pipe sensor (Inverter)• Open / Short
• Soldered poorly
• Internal circuit error
• Normal resistor: 200K£2 / at 25°C (Unplugged)
• Normal voltage : 4.5Vdc / at 25°C (plugged)
44Air sensor-• Normal resistor: 10K£2 / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
45Condenser Pipe sensor-• Normal resistor: 5K£2 / at 25°C (Unplugged)
46Suction Pipe sensor-• Normal voltage : 2.5Vdc / at 25°C (plugged)
47D-pipe sensor (Constant)-• Normal resistor: 200K£2 / at 25°C (Unplugged)
• Normal voltage : 4.5Vdc / at 25°C (plugged)
65Heat sink sensor-• Normal resistor: 10K£2 / at 25°C (Unplugged)
• Normal voltage : 2.5Vdc / at 25°C (plugged)
51Over capacity• Over capacity• Check the indoor unit capacity.
• Check the combination table.
60EEPROM Check sum• Check sum error• Check the PCB ASM P/No.
• Check the poor soldering.
61Condenser pipe sensor temp, high• Condenser pipe sensor detected high temp.(65°C)• Check the load condition.
• Check the sensor of Condenser pipe sensor.
62Heat sink sensor temp, high• Heat sink sensor detected high temp.(85°C)• Check the fan is locked.
• Check the sensor of heat sink.
май.53Title Communication (Indoor - Outdoor)• Communication poorly• Power input AC 220V. (Outdoor, Indoor)
• The connector for transmission is disconnected.
• The connecting wires are misconnected.
• The communication line is shorted at GND.
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.
21DC PEAK (IPM Fault)• Instant over current
• Over Rated current
• Poor insulation of IPM
• An instant over current in the U,V,W phase
- Comp lock
- The abnormal connection of U,V,W
• Overload condition
- Overcharging of refrigerant
Pipe length.
Outdoor Fan is stop
• Poor insulation of compressor

Error CodeFunction NameDescription
01 hRead Coil StatusRun/Stop(status), Lock(status), Swing(status), Alarm, Filter Sign(status), Mode Lock(status), Wind Flow Lock(status)
03hRead Holding RegistersOperation Mode(status), Fan Speed(status), Room Temperature, Error Code,
Set Room Temperature(status),
Set Lower Temperature(status),
Set Upper Temperature(status),
User Mode(status)
05hForce Single CoilRun/Stop(setting), Lock(setting), Swing(setting), Filter Sign Reset, Mode Lock(setting),
Wind Flow Lock(setting)
06hPreset Single RegistersOperation Mode(setting), Fan Speed(setting), Set Room Temperature(setting),
Set Lower Temperature(setting),
Set Upper Temperature(setting),
User Mode(setting)

Error CodePossible CauseIndicatorOperating State
2Outdoor TH. is short or open.The operating LED will be blinking twice.Keep operating state.
4Temp. of Heat sink is over 95°C. Heat sink TH. is short or open.The operating LED will be blinking 4 times.Restart compressor when Heat sink
Temp is 85°C below.
5Communication error (serial communication).The operating LED will be blinking 5 times.The operation is off (enable to restart by remote controller).
6DC peak error.The operating LED will be blinking 6 times.Compressor will be turned off immediately (not enable to restart by remote controller)
7Running current is overloaded.The operating LED will be blinking 7 times.Compressor will be turned off immediately (not enable to restart by remote controller)
9Outdoor fan lock error (BLDC fan model)The operating LED will be blinking 9 times.The operation is off (enable to restart by remote controller).
10D-PIPE TH is short or open.The operating LED will be blinking 10 times.Compressor will be turned off immediately (restart compressor when D-PIPE TH. is recovered)

Error CodePossible CauseCheck/RepairShop Parts
1Temperature sensor failureUnplug the air conditioner and check the wire harness connections on the electronic control board. Examine the electronic control board for damage. Check for a pinched or broken wire in the temperature sensor wire harness. Replace the temperature sensor if it’s defective.Temperature sensor, Wire harness, Electronic control board
E2Failure in the indoor temperature sensorUnplug the air conditioner and check the wire harness connections on the electronic control board. Examine the electronic control board for damage. Check for a pinched or broken wire in the indoor temperature sensor wire harness. Replace the indoor temperature sensor if it’s defective.Indoor temperature sensor, Wire harness, Electronic control board
E3Abnormal operation protection errorIndoor temperature sensor, Wire harness, Electronic control board
E3Clean or replace filters if dirty. Unplug the window air conditioner and check all components for visible damage. Check fan blades for damage or obstructions and replace any damaged fan blades. Check all wire harness connections. Replace any damaged wire harnesses.Filter, Fan blade, Fan motor, Wire harness
E4 (Portable A/C only)The air conditioner is in the defrost modeAfter the air conditioner exits defrost mode and resume normal operation, check the unit to see if it’s cooling properly. If so, then the E4 code is normal. If the portable air conditioner frequently goes into the defrost mode and isn’t cooling properly, check the air filters and clean or replace filters if dirty.Filter
P2 or FL (Portable A/C only)The water collection tank is fullEmpty the water collection tank. If the P2 or FL code appears when the tank is empty, replace the float switch or sensor in the collection tank.Collection tank float switch or sensor

 