Day and Night Air Conditioner Error Codes


Day and Night Air Conditioner Error Codes
Error Code
Problem
E1
High pressure protection
E2
Stop for anti?freeze protection of indoor ?unit
E4
Stop for discharge temp protection
E5
Stop for low voltage protection
E6
Stop for communication malfunction
H1
Automatic defrosting
H3
Stop for compressor overload protection
H4
Overload protection
H5
Stop for IPM module protection
H6
DC motor (indoor unit) does not operate
HC
PFC overcurrent malfunction
F1
Indoor ambient temperature sensor malfunction
F2
Indoor tube temperature sensor malfunction
F3
Outdoor ambient temperature sensor malfunction
F4
Outdoor tube temperature sensor malfunction
F5
Outdoor discharge temperature sensor malfunction
PH
DC voltage is too high
PL
Low voltage protection
L9
High power protection
LP
Unit match protection
U8
Indoor fan speed detection circuit malfunction
U9
System current too high
C5
Jumper connection malfunction protection
Overload protection
If temperature sensed by the overload sensor is over 239°F, the compressor will stop and the outdoor fan will stop with a time lag of 30 seconds. If the temperature drops below 203°F, the overload protection will be reset.
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time lag of 30 seconds. When voltage on the DC bus returns to its normal value and the compressor has stayed at a stop for at least 3 minutes, the compressor will resume its operation. Faults of temperature sensors.

Day and Night Air Conditioner Remote Control
Description of Sensors: Indoor Ambient Temperature
Faults: The sensor is open or short−circuited for 30 consecutive seconds
Description of Sensors: Indoor Tube Temperature
Faults: The sensor is open or short−circuited for 30 consecutive seconds
Description of Sensors: Outdoor Ambient Temperature
Faults: The sensor is open or short−circuited for 30 consecutive seconds
Description of Sensors: Outdoor Tube Temperature
Faults: The sensor is open or short−circuited for 30 consecutive seconds, and no detection is performed within 10 minutes after defrost begins
Description of Sensors: Exhaust
Faults: After the compressor has run for 3 minutes, the sensor is open or short−circuited for 30 consecutive seconds