Chigo Air Conditioner Error Codes


Chigo Air Conditioner Error Codes

Error Codes
Solution
E1
Condenser temperature aensor fault
E2
Room temp. sensor fault
E3
Coil temp. sensor fault
E4
Outdoor unit abnormal
E5
No feedback signal of indoor fan
E6
No over zero signal
E7
Outdoor feedback fault
E8
Frost protection/over heat protection
F1
Communication fault
F2
Ambient temp. sensor fault
F3
Coil pipe temp. sensor of indoor unit fault
F4
Fan motor of indoor
F5
Module of outdoor unit fault
F6
Ambient temp. sensor of outdoor fault
F7
Coil pipe temp. sensor of outdoor unit fault
F8
Suction temp. sensor of compressor fault
F9
Discharge temp. sensor of compressor fault
FA
Inductor of current or voltage fault
FC
Compressor drive fault
FD
Phase lacking or phase sequence fault
FE
Gas return sensor fault
FF
Other fault
P1
Temp. of evaporator protection
P2
Overheat, over current protection of inverter module
P3
Over current protection
P4
Discharge temp. of compressor protection
P5
Over heat of compressor top protection
P6
Suction temp. of compressor protection
P7
Low or high voltage protection
P8
Low presser of gas return protection
P9
High pressure of discharge protection
PA
High temp. of condenser protection
PC
High temp. of outdoor ambient protection
PF
Other protection
DF
Defrost indication
Content:
  1. Wall Split AC Series
  2. Floor Standing AC Series
  3. Portable AC Series
  4. Dehumidifer
  5. DC Inverter Single Split Series
  6. DC Inverter Multi-Split Series
  7. VRF System Error Codes
1. Wall Split AC Series Error Codes;
Chigo Wall Split AC Series Error Codes
Code: DF
Failure: Defrost indication
The reason of fault and solution: Normal, the defrost state is removed, it will return to normal condition automatically
Code: E2
Failure: Room temp. sensor fault
The reason of fault and solution:
  1. Check whether the resistance of the sensor is normal (the resistance is 5КΩ in the normal temperature 25 ) , when it is abnormal the sensor should be replaced.
  2. Check whether there is short circuit or open circuit in the wire of the sensor, and whether the plug is connected well, whether there is welding off or rosin joint on the electric control board, if there is any, it should be repaired.
  3. When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced.
Code: E3
Failure: Coil temp. sensor fault
The reason of fault and solution:
  1. Check whether the resistance of the sensor is normal (the resistance is 5КΩ in the normal temperature 25 ) , when it is abnormal the sensor should be replaced.
  2. Check whether there is short circuit or open circuit in the wire of the sensor, and whether the plug is connected well, whether there is welding off or rosin joint on the electric control board, if there is any, it should be repaired.
  3. When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced.
Code: E4
Failure: Outdoor unit abnormal
The reason of fault and solution:
  1. Check whether the winding resistance and operation current of the compressor are normal.
  2. Check whether the high and low pressure is normal when the unit is running.
  3. Check (whether the coil pipe sensor is normal) whether the contact of the inserter on the circuit board is well, the coil pipe temperature sensor is fixed, the evaporation of the indoor unit is well, the key is to check the evaporator temperature detected by the coil pipe temperature sensor has reached the cooling or heating temperature.
  4. Check whether the surface of the condenser is too dirty, it should be cleaned when it is too dirty.
  5. Check whether the capacitance of the outdoor motor and the fan is damaged, it should be replaced when
Code: E5
Failure:  No feedback signal of indoor fan
The reason of fault and solution:
  1. Check whether two sets of plugs on the outlet end of the motor have loosed from the socket of the electric control board, insert it firmly when loosing.
  2. Check whether the indoor motor has damaged, the motor should be replaced when it is damaged
  3. Check whether the controllable silicon and other components on the electric control board have damaged, replace the controllable silicon or electric control board when they are damaged.
Code: E6
Failure: No over zero signal
The reason of fault and solution:
  1. Firstly check whether the indoor fan is normal.
  2. Check whether the signal outputting from the integrated chip of the electric control board is normal, the electric control board should be replaced when the signal is abnormal.
Code: E7
Failure: Outdoor feedback fault
The reason of fault and solution:
  1. Check whether the winding resistance and operation current of the compressor are normal
  2. Check whether the high and low pressure is normal when the unit is running.
  3. Check whether the indoor and outdoor wiring is right; when it is wrong, connect them again according to the circuit diagram
  4. Check whether the contact of the inserter on the circuit board and the connection are well, otherwise repair.
  5. Check whether the signal feedback wire is disconnected, replace or connect the feedback signal wire.
  6. Check whether the supply power is phase-lacking or phase opposition.
  7. Check whether the AC electromagnetic contactor is well.
Code: E8 
Failure: Frost protection/over heat protection
The reason of fault and solution:
  1. Check whether the filter of the indoor unit is dirty or blocked, and clean if it is dirty.
  2. Check whether the indoor fan is running normally, and replace the motor if it is abnormal.
  3. Check whether indoor pipe temperature sensor is normal, and replace the sensor if it is abnormal.
  4. Check whether the system pressure is normal, if abnormal, should check whether there is leakage, and fill the refrigerant again.