Amana Ac Error Codes And Troubleshooting
Follow These Simple
Steps To Manuely Reset Your Complete Amana Ac Error Codes.
- Make
sure the unit is plugged in.
- Carefully
lift off the front plastic cover by lifting up and pulling toward you.
- Turn
off the master power switch under the control panel. Leave off for at
least 5 seconds.
- Push
and hold both the heat and
cool buttons.
- While
holding the buttons, turn the master switch back on.
- When the
red light appears next to the off button, the system has been successfully
reset.
- Place
the front plastic cover back onto the unit and enjoy!
- Hope All Of Do This You Cover Up Your Problem
If Not Solved So Simply Contact Us We
Are Available For You Every Time.
Amana packaged terminal
air conditioner units are known for their reliability, but as with any product,
things can go wrong. If you are ever having trouble with an Amana
PTAC a quick reset might be the easiest way to fix the problem. The manual
reset process with clear any settings that you have changed and return
everything back to the factory default.
If there are no active
failures or lockouts, the display will show a double dash, “- -”. If there is a
code listed, see the unit “Diagnostic Codes” chart for a list of definitions.
Error Codes
|
Problem
|
FP
|
Freeze Protection Engaged. The room temperature measured
by the wireless remote thermostat or indoor ambient thermistor active sensor
falls below 40°F. No Action required. This setting will disengage when the
room temperature rises above 43°F.
|
Fd
|
Front Desk switch is closed. All outputs are switched off.
Open front desk switch to allow occupant unit operation.
|
Eo
|
Un-Configured Service Board - All operation held awaiting
configuration. Enter Configuration Menu and set "C3" to
"C" for coolers with electric heat or "H" for heat pumps.
|
EH
|
Emergency Hydronic Engaged. The EHH switch is closed.
Compressor is switched off. Open front emergency hydronic switch to allow
occupant unit operation.
|
LS
|
Load Shedding Engaged. The LS switch is closed. Compressor
and Electric heat is switched off. Open load shedding switch to allow
occupant unit operation.
|
On
|
Control is configured to respond to a wired thermostat. No
action if a wired thermostat is being used. Otherwise, see Configuration
Settings.
|
oP
|
Open Door Lockout (DS1 & DS2 open; wireless). Close
Room Door. Unit will not condition space with door open.
|
nP
|
Window Switch Lockout - (LS & INN open). Close Room
Door or Window. Unit will not condition space with door or window open.
|
HP
|
Heat Sentinel - (WIAT > u3). No action required. This
setting will disengage when the room temperature falls.
|
Un-Rented Status (EHH & INN or wireless). Front Desk
needs to set to Rented mode (if applicable).
|
|
F1
|
Indoor Ambient Thermistor reads outside the range -20°F to
200°F & the wireless thermostat is not communicating to the unit control
or Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads
outside the range -20°F to 200°F. Replace black Indoor Ambient Thermistor or
Wireless Remote Thermostat.
|
F2
|
Wireless Remote Thermostat failure. Replace Wireless
Thermostat.
|
F3
|
Indoor Ambient Thermistor reads outside the range -20°F to
200°F. Replace black Indoor Ambient Thermistor.
|
F4
|
Indoor Coil Thermistor either above or below operating
tolerances. Replace Red Indoor Coil Thermistor.
|
F5
|
Wireless Thermostat failure. Attempt to rebind Wireless
Thermostat or Replace Wireless Thermostat.
|
F6
|
Indoor Discharge Thermistor either above or below
operating tolerances. Replace Yellow Indoor Discharge Thermistor.
|
Fb
|
Low Remote
|
H1
|
High Voltage Protection engaged. Power supply voltage is
to high. Check for incoming power at correct voltage.
|
br
|
Brown Out Protection engaged. Power was lost or voltage is
low. Check for incoming power at correct voltage.
|
L6
|
Discharge Air Too Hot. Clean Filter or Remove Air Blockage.
|
LC
|
Outdoor Coil Thermistor temperature is high. Clean
Condenser Coils, Check Fan for fault. Code will reset after cleaning.
|
C2
|
Indoor Air Recirculation. Large delta between thermostat
and return. Clean Filter or Remove Air Blockage or Close Vent Door or Improve
indoor to outdoor seal.
|
C5
|
Outdoor Coil temperature too high for outdoor ambient
temperature. Check for Blocked Outdoor Air or Clean Coil.
|
C1
|
Indoor Coil is freezing up. Clean filter, Check for fan
and blower operation, Check for Refrigerant loss or Restricted capillary
tube.
|
C3
|
Indoor Coil is freezing up. Clean filter, Check for fan
and blower operation, Check for Refrigerant loss or Restricted capillary
tube.
|
C4
|
Indoor Coil froze up. Clean filter, Check for fan and
blower operation, Check for Refrigerant loss or Restricted capillary tube.
|
C6
|
Poor Unit Performance. Check for blower motor, compressor,
or electric heat operation.
|
C7
|
Indoor Freezing Lockout (ICT - IAT > 20) +10 Min. Clean
filter, Check for fan and blower operation, Check for Refrigerant loss or
Restricted capillary tube.
|