Panasonic Air Conditioner Error Codes


Panasonic Air Conditioner Error Codes

Error Code
Cause
S01
Room temperature sensor failure
S02
Indoor coil sensor failure
S03
Humidity sensor failure
S04
Comp. temperature sensor failure
S05
Outdoor coil sensor failure
S06
Outdoor air sensor failure
S07
Outdoor current sensor failure
E01
Indoor/outdoor communication failure
E02
HIC circuit failure (Compressor/Fan circuit)
E03
Outdoor unit OTP rom failure
E04
Peak current cut off
E04
PAM or Active circuit failure
E05
High compressor discharge temperature
E06
Indoor fan operating failure
E07
Way valve switching failure (RV)
E08
No refrigerant protection
E09
DC compressor drive circuit failure
E10
Outdoor fan operating failure
E11
Error in outdoor unit

Panasonic Air Conditioner Troubleshooting


Panasonic Air Conditioner Troubleshooting
The following symptoms do not indicate malfunction;
Symptom: Mist emerges from indoor unit.
Cause: Condensation effect due to cooling process
Symptom: Water fl owing sound during operation.
Cause:  Refrigerant fl ow inside the unit.
Symptom: The room has a peculiar odour
Cause: This may be due to damp smell emitted by the wall, carpet, furniture or clothing
Symptom: Indoor fan stops occasionally during automatic fan speed setting.
Cause:  This helps to remove the surrounding odour
Symptom: Airflow continues even after operation has stopped
Cause:  Extraction of remaining heat from the indoor unit (maximum 30 seconds).
Symptom: Operation is delayed a few minutes after restarting
Cause:  The delay is a protection to the unit’s compressor.
Symptom: Outdoor unit emits water/steam
Cause:  Condensation or evaporation occurs on pipes
Symptom: POWER indicator blinks during HEAT mode with no warm air supply (and louver is closed)
Cause: The unit is in defrost mode (and AIR SWING is set to AUTO).
Symptom: Indoor fan stops occasionally during heating operation.
Cause: To avoid unintended cooling effect
Symptom: POWER indicator blinks before the unit is switched on.
Cause:  This is a preliminary step in preparation for the operation when the ON timer has been set
Symptom: Cracking sound during operation
Cause: Changes of temperature caused the expansion/contraction of the unit
Symptom: POWER indicator blinks 3 seconds ON and 0.5 seconds OFF during operation
Cause: The unit is in Demand Response Mode
Check: the following before calling for servicing
Symptom: Operation in HEAT/COOL mode is not working efficiently
Check:
  • Set the temperature correctly.
  • Close all doors and windows.
  • Clean or replace the fi lters.
  • Clear any obstruction at the air inlet and air outlet vents
Symptom: Noisy during operation
Check:
  • Check if the unit has been installed at an incline
  • Close the front panel properly
Symptom: Remote control does not work
Check:
  • Insert the batteries correctly
  • Replace weak batteries
Symptom: The unit does not work
Check:
  • Check if the circuit breaker is tripped.
  • Check if timers have been set
Symptom: The unit does not receive the signal from the remote control.
Check:
  • Make sure the receiver is not obstructed.
  • Certain fl uorescent lights may interfere with signal transmitter. Please consult authorised dealer