Mcquay Cassette Split Air Conditioning Error Codes


Mcquay Cassette Split Air Conditioning Error Codes
Wired Remote Control (Universal Board)
Models:
MCK 020A/AR  MCK 025A/AR   MCK 030A/AR 
MCK 040A/AR   MCK 050A/AR   MCK 015B/BR
MCK 020B/BR    MCK 025B/BR    MCK/M5CK 010C/CR
MCK/M5CK 015C/CR      MCK 020C/CR


E1-E2-E3-E4-E5-E6
Water Pump
The water pump will on if compressor is on during cooling cycle. The pump will remain on for at least 5 minutes after the compressor is off.
During mode change from cooling to non-cooling mode, the pump will on for minimum 5 minutes. During defrost cycle, the pump will on and will on for another 5 minutes once the defrost cycle is terminated.
Water level Switch
This normally close switch is to detect faults in water pump system. It will confirm for 30 seconds for switch open and 60 seconds for switch close. Once switch is confirmed open, it will force compressor to cut off. If the switch is closed within 5 minutes, the compressor is allowed to cut in. If the switch does not close for more than 5 minutes, the system will warn user regarding the fault, the compressor is not allowed to cut in. If the switch is confirmed opened twice within 30 minutes, the system assumes there are faults.

Phase Sequencer